Fire Dynamics Simulation of 2011 Baltimore County LODD- 30 Dowling Circle

No comments

Operations at 30 Dowling Circle 01.19.2011 Box 11-09

 On Wednesday, January 19, 2011, a fire occurred in an apartment building located in the Hillendale section of Baltimore County, Maryland. This fire resulted in the line of duty death (LODD) of volunteer firefighter Mark G. Falkenhan, who was operating as the acting lieutenant on Squad 303 . Upon their arrival, FF Falkenhan and a second firefighter from Squad 303 deployed to the upper floors of the apartment building to conduct search and rescue operations. Other fire department units were already involved with both firefighting operations and effecting rescues of trapped civilians.

During these operations, FF Falkenhan and his partner became trapped in a third floor apartment by rapidly spreading fire and smoke conditions. The second firefighter was able to self-egress the building by diving headfirst down a ladder on the front (address side) of the building. FF Falkenhan declared a “MAYDAY” and implemented “MAYDAY” procedures, but was unable to escape or be rescued.

FF Falkenhan was located and removed via a balcony on the third floor in the rear of the building. Resuscitative efforts began immediately upon removal from the balcony, and continued en route to the hospital. FF Falkenhan succumbed to his injuries and was pronounced deceased at the hospital.

Mark Gray Falkenhan had dedicated his life to serving others. He perished in the line of duty on January 19, 2011 while performing search and rescue operations at a multi-alarm apartment fire in Hillendale, Baltimore County (Maryland). He was 43 years old.

 

Firefighter Mark Falkenhan

30 Dowling Circle

 

The Baltimore County (MD) Fire Department published the Line of Duty Death Investgation Report of the 30 Dowling Circle Fire recently.

The report was written by a Line of Duty Death Investigation Team comprised of departmental members, including representatives of the local firefighters’ union and the Baltimore County Volunteer Firemen’s Association.

An overview and executive narrative of the final report (PDF) on the apartment fire where Volunteer Firefighter Mark Falkenhan sustained fatal injuries was posed on CommandSafety.com HERE.

FF Mark Falkenhan

 On Wednesday, January 19, 2011, a fire occurred in an apartment building located in the Hillendale section of Baltimore County, Maryland. This fire resulted in the line of duty death (LODD) of volunteer firefighter Mark G. Falkenhan, who was operating as the acting lieutenant on Squad 303 (for purposes of this report, Mark will be referred to as FF Falkenhan).

Upon their arrival, FF Falkenhan and a second firefighter (FF # 2) from Squad 303 deployed to the upper floors of the apartment building to conduct search and rescue operations. Other fire department units were already involved with both firefighting operations and effecting rescues of trapped civilians.

During these operations, FF Falkenhan and FF # 2 became trapped in a third floor apartment by rapidly spreading fire and smoke conditions. FF # 2 was able to self-egress the building by diving headfirst down a ladder on the front (address side) of the building. FF Falkenhan declared a “MAYDAY” and implemented “MAYDAY” procedures, but was unable to escape or be rescued.

FF Falkenhan was located and removed via a balcony on the third floor in the rear of the building. Resuscitative efforts began immediately upon removal from the balcony, and continued en route to the hospital. FF Falkenhan succumbed to his injuries and was pronounced deceased at the hospital.

The investigating team examined any and all data available, including independent analysis of the self contained breathing apparatus (SCBA), turnout gear and autopsy report. The Bureau of Alcohol, Tobacco, Firearms and Explosives (ATF) produced a fire model to assist with evaluating fire behavior. Multiple site inspections were conducted. Extensive interviews were conducted by the team which also attended those conducted by investigators from the National Institute for Occupational Safety and Health (NIOSH). Photographic and audio transcripts were also thoroughly analyzed. A comprehensive timeline of events was developed. All information used to make decisions regarding recommendations was corroborated by at least two sources.

  • In fairness to those units involved in this incident, the investigating team had the advantage of examining this incident over the period of several months. Furthermore, given the size and nature of the event, and the fact that arriving crews were met with serious fire conditions and several residents trapped and in immediate danger, all personnel should be commended for their efforts for performing several rescues which prevented an even greater tragedy.
  • The team did not identify a particular primary reason for FF Falkenhan’s death.
  • What were identified were many secondary issues involving but not limited to crew integrity, incident command, strategy and tactics, and communications.
  • These issues are identified and discussed, and recommendations are made in appropriate sections of the report, as well as in a consolidated format in the Report Appendix.

Some of the issues identified in this report may require some type of change to current practices, policies, procedures or equipment. Most, however, do not. Specifically, the analysis and recommendations regarding Incident Command and Strategy and Tactics show that if current policies and procedures are adhered to, the opportunity for catastrophic problems may be reduced.

  • Mark Falkenhan was a well-respected and experienced firefighter.
  • He died performing his duties during a very complex incident with severe fire conditions and unique fire behavior coupled with the immediate need to perform multiple rescues of victims in imminent danger.
  • It would be easy if one particular failure of the system could be identified as the cause of this tragedy.
  • We could fix it and move on. Unfortunately it is not that simple.
  • No incident is “routine”. Mark’s death and this report reinforce that fact.

On Wednesday, January 19, 2011 at 1816 hours, a call was received at the Baltimore County 911 Center from a female occupant at 30 Dowling Circle in the Hillendale section of Baltimore County. The caller stated that her stove was on fire and the fire was spreading to the surrounding cabinets. Fire box 11-09 was dispatched by Baltimore County Fire Dispatch (Dispatch) at 1818 hours consisting of four engine companies, two truck companies, a floodlight unit, and a battalion chief. All units responded on Talkgroup 1-2.

The location, approximately one mile from the first dispatched engine company, is a three story garden-type apartment complex, with brick construction and a composite shingle, truss supported roof. The fire building contained a total of six apartments divided by a common enclosed stairway in the center with one apartment on the left and one to the right of the stairs.

 

Fire Dynamics Simulation of 2011 Baltimore County LODD- 30 Dowling

Fire Dynamics Analysis and Insights

 

INTRODUCTION:

Assistance from the Bureau of Alcohol, Tobacco, Firearms and Explosives (ATF) Fire Research Laboratory (FRL) was requested for a fire at 30 Dowling Circle by the Baltimore County Fire Investigation Division (FID) through the ATF Baltimore Field Division on the night of January 19, 2011.

ATF Fire Protection Engineers were asked to utilize engineering analysis methods, including computer fire modeling, to assist with determining the route of fire spread and the events that led to the firefighter MAYDAY and subsequent Line of Duty Death.

Download the REPORT HERE

BACKGROUND:

Working closely with the Post Incident Analysis Team, the ATF Fire Research Laboratory created a computer simulation of the garden apartment building using Fire Dynamics Simulator (FDS). FDS is a computational fluid dynamics (CFD) modeling program developed by the National Institute of Standards and Technology (NIST).

FDS utilizes mathematical calculations to predict the flow of heat, smoke and other products of fire. Smokeview, a post-processer computer program also produced by NIST, was then used to visualize the mathematical output from FDS. The most current available versions of both programs were used: FDS 5.5.3 and Smokeview 5.6. Below are photographs of the front and rear of the fire building next to an image of the same building constructed in FDS.

Figure 01. 30 Dowling Street

 

Figure 2. FDS representation of the front of 30 Dowling Circle showing the terrace (T), second (A) and third (B) levels.

 

The garden apartment building at 30 Dowling Circle was attached to two similar garden apartment buildings, one on each side. The fire damage was isolated to 30 Dowling Circle, so the exposure buildings were not included in the computer fire model. The entire six unit garden apartment building was modeled in FDS, including the patio and balconies on the rear of the building. FDS works by dividing a space into cubical “grid cells” for calculation purposes. FDS then computes various CFD calculations for each grid cell to predict the movement of mass, energy, momentum and species throughout a three-dimensional space.

The Dowling Circle model consisted of 2,560,000 total grid cells that were each 3.9 inch (10 cm) cubes. The model was used to simulate a total elapsed real time of 27.5 minutes, beginning before the 911 call and ending just after flashover of the third floor and the firefighter MAYDAY.

The model was synchronized in real time with the fireground audio throughout the duration of the fire.

Fiqure 03 and 04

 

FDS has been validated to predict the movement of heat and smoke throughout a compartment, however the accuracy of fire modeling depends on it being used appropriately by a trained user that is aware of its limitations. Due to lack of knowledge about the exact material properties for the various furnishings and other available fuels, a user-specified fire progression was used for this application.

For flame and fire gas movement after consumption of the original burning fuel packages, the fire model calculated smoke and ventilation flow paths through the building and was used to gain a better understanding of the rapid fire growth leading to flashover of the stairwell and third floor.

  • In addition, FDS was utilized to illustrate the complex route of fire spread through the building as verified by witness statements, firefighter interviews, photographs and burn patterns.
  • Input data for the computer model included heat release rate data and video from previous testing conducted by the ATF FRL and NIST.
  • Ambient weather data was also input into the model, including temperature, as well as wind direction and magnitude at the time of the fire. In addition, several alternative compartmentation scenarios were modeled to explore the possible effects of closed stairway apartment entrance doors on the spread of smoke and flames in the stairwell.
  • The statements of each firefighter were reviewed and their individual actions (breaking windows, opening doors, etc.) and observations (fire size, smoke conditions, etc.) were recorded on floor diagrams.

The actions and observations of the firefighters were then associated with specific times in the fireground audio to generate an overall event timeline. All events in the model are based on this master timeline of events. In addition, all photographs were time stamped and synchronized with the model. The Post Incident Analysis Team was consulted throughout the development of the event timeline and the computer fire model to ensure accuracy.

MODELING ANALYSIS:

1. Analysis of Fire Development in the Terrace Level

The fire originated on the stovetop of an occupied apartment on the right (south) side of the terrace level (apartment T2). Flames from a grease fire ignited kitchen cabinets, eventually causing the kitchen to flashover into the attached living room. Upon fire department arrival, a fully developed fire existed in the living room and kitchen of apartment T2. Prior to exiting the apartment, the occupant opened both the rear sliding door and the apartment entrance door in an attempt to ventilate smoke from the apartment.

 

Figure 06. A typical floor plan of the right side apartments at 30 Dowling Circle.

 

An analysis of the ventilation flow path through the apartment with FDS indicated that a significant unidirectional flow path existed up the stairs with an inlet at the rear terrace sliding door and outlet at the front apartment entrance door leading to the stairwell.

Figure 7. Smokeview frame of the rear of the building indicating the fire origin and smoke spread within the T2 apartment. Figure 8. View of smoke flow out of kitchen and open sliding glass door (center of photo) in the rear of apartment T2. Figure 9. Smokeview frame of flashover of the kitchen with flames extending into the living room. Flames also begin to extend out of the rear sliding door and impact the balcony above.

 

Figure 10. Ignition of second level balcony resulting from flame extension from living room.

 

This unidirectional flow path up the stairs is difficult to combat and is often experienced during basement fires as crews attempt to descend interior stairs. The model indicates sustained air temperatures in the stairwell of approximately 600 Fahrenheit (315 Celsius) at velocities of approximately 6 mph (2.7 m/s) from floor to ceiling as crews attempted to descend the stairs. This is consistent with statements from firefighting crews, who experienced extremely high heat conditions and indicated periodically seeing flames in the smoke layer flowing up the stairs.

The elevated air velocity of the stairwell flow path resulted in a high rate of convective energy transfer to the structural firefighting gear and high perceived temperatures as the firefighters attempted to descend the stairs. Firefighting crews flowed a hoseline down the stairs to combat the high temperatures; however no significant cooling was noticed by firefighters because the hose stream could not reach the seat of the fully developed fire in the kitchen area.

The crews were simply cooling the ventilation flow path without cooling the source of the energy in the apartment. It was not until a hose stream was directed through an exterior window and a portion of the fire was extinguished that gas temperatures and velocities began to decrease, allowing firefighters to make entry to the terrace apartment via the stairs.

Figure 12. Smokeview section frame showing unidirectional flow of approximately 600 Fahrenheit (315 Celsius) gases out of the stairwell entrance door

Front photo of unidirectional flow of smoke up stairwell from apartment T2. Note the high volume of smoke from floor to ceiling as the stairwell door serves as the flow path outlet. The ground ladder in the foreground was used to rescue an occupant on the third floor trapped by heavy smoke in the stairwell. (Refer to Figure 014)

Figure 014. Front photo of unidirectional flow of smoke up stairwell from apartment T2. Note the high volume of smoke from floor to ceiling as the stairwell door serves as the flow path outlet.

 

The first arriving engine, E-11, was staffed with a Captain, Lieutenant, Driver/Operator, and a Firefighter. Upon arrival at 1820 hours, the Captain gave a brief initial report describing a three story garden apartment with smoke showing from side Alpha: “The Captain of E-11 will have Command and we are initiating an aggressive interior attack with a 1 ¾” hand line”. Command also instructed the second due engine to bring him a supply line from the hydrant. 

A female resident (victim # 1) appeared in a third floor apartment window, Alpha/Bravo side (Apt. B-1), yelled for assistance, and threatened to jump. Smoke or fire was visible from any of the third floor windows. At 1823 hours, Command advised Dispatch that he had a rescue and that he was establishing Limited Command. Fire Dispatch was in the process of upgrading the response profile to an apartment fire with rescue when the responding Battalion Chief requested that the fire box be upgraded to a fire rescue box. While the Firefighter and Lieutenant prepared for entry into the building, the Captain and Driver/Operator extended a ladder to the 3rd floor apartment window and rescued the resident. The first attempt by the Firefighter and Lieutenant to make entry into the side Alpha entrance was unsuccessful due to the extreme heat and smoke conditions.

The second due engine, E-10, arrived at 1823 with staffing of a Captain, Lieutenant, Driver/Operator, and a Firefighter. At 1823, E-10’s crew brought a 4″ supply line to E-11 from the hydrant at Deanwood Rd. and Dowling Circle and assisted the first-in crew with fire attack.

  • The Captain from E-10 conferred with Command and was instructed to advance a second 1 ¾” hand line.
  • The window to the first floor right apartment (Apt. T-2) was removed, and the second 1 ¾” line was advanced to the building by the crew of E-10.
  • Fire attack was initiated through the removed window. At 1827, Command requested a second alarm.

At this time, heat and smoke conditions just inside the front door improved enough to allow the Firefighter and Lieutenant from E-11 to make entry through the front door and into the stairwell. There they encountered heavy, thick black smoke and high heat conditions coming up the stairs from the terrace level apartment. The Lieutenant reported that the doorway to the first floor apartment was orange with fire and he had to fight his way through heavy heat and smoke conditions to attack the fire in the first floor right apartment (Apt. T-2). Entry was made approximately 3 feet into the doorway when the Firefighter’s low air alarm began to sound, and he exited the building. A member from E-10’s crew replaced the Firefighter from E-11 on the hose line.

At the same time, the Captain from E-11 proceeded to the rear of the structure to complete his initial 360 degree size up. He noted that there was fire emanating from the open sliding doors on the first floor Charlie/Delta apartment (Apt. T-2), extending to the balcony above. E-1, staffed by a Captain, Driver/Operator, and two Firefighters arrived and completed the hookup of the supply line that had been laid to the hydrant by E-10. The rest of Engine 1’s crew grabbed tools and an extension ladder and reported to the Charlie side of the building.

Figure 015 Charlie Side ( Rear) Extension

The Photo above referenced as  Figure 015 shows conditions  from rear of flames in apartment T2 and extension to the balcony above. Note the relative minimal volume of smoke as the sliding door serves as the inlet for ventilation into the apartment. The smoke and heat is flowing in from the rear, through the apartment and up the stairs.

This unidirectional flow path up the stairs is difficult to combat and is often experienced during basement fires as crews attempt to descend interior stairs.

  • The model indicates sustained air temperatures in the stairwell of approximately 600 Fahrenheit (315 Celsius) at velocities of approximately 6 mph (2.7 m/s) from floor to ceiling as crews attempted to descend the stairs.
  • This is consistent with statements from firefighting crews, who experienced extremely high heat conditions and indicated periodically seeing flames in the smoke layer flowing up the stairs.
  • The elevated air velocity of the stairwell flow path resulted in a high rate of convective energy transfer to the structural firefighting gear and high perceived temperatures as the firefighters attempted to descend the stairs.

Firefighting crews flowed a hoseline down the stairs to combat the high temperatures; however no significant cooling was noticed by firefighters because the hose stream could not reach the seat of the fully developed fire in the kitchen area.

The crews were simply cooling the ventilation flow path without cooling the source of the energy in the apartment.

It was not until a hose stream was directed through an exterior window and a portion of the fire was extinguished that gas temperatures and velocities began to decrease, allowing firefighters to make entry to the terrace apartment via the stairs.

Plan view of flow path and temperatures within the apartment. Note the location of the seat of the fire and the location of initial hose stream application down the stairs.

Figure 016

 

Photograph of hoselines being positioned at the stairwell entrance door and front window. Note the heavy smoke venting from all front openings in apartment T2. (Figure 017)

Figure 017 Alpha Side Entry Door

 

Figure 017  Hoselines being positioned at the stairwell entrance door and front window. Rapid Fire Progression Leading to Flashover of the Third LevelFlames extended upwards from the T2 apartment sliding door and ignited the rear balconies of the second and third level apartments above.
 
Fire on the second floor balcony extended into apartment A2 by failing the sliding glass door and igniting vertical plastic slat curtains that were suspended above.As crews searched within the second floor apartment, they noted seeing the burning curtains on the floor with flames extending to a nearby couch (containing polyurethane foam padding) adjacent to the sliding doorway.
 
The fire continued to grow unsuppressed and spread to a second couch as interior firefighting crews were engaged in rescuing two victims from the living room in the second floor apartment.Personnel stated that at this point fire conditions seemed to improve, suggesting that crews were making progress extinguishing the fire. (The first arriving attack crew reported that they were able to see apparatus lights through the sliding doors on Charlie side, which indicated to them that smoke and fire conditions were improving.)Truck 1, a tiller unit staffed by a Lieutenant, two Driver/Operators, and a Firefighter, arrived on side Alpha and immediately began search and rescue operations.
 
Windows on the second floor Alpha/Delta side apartment (Apt. A-2) were vented and ladders were thrown to gain access. T-8 arrived at the alley on side Charlie. E-1 extended a ground ladder to the third floor balcony on the Charlie/Bravo side of the structure (Apt. B-1), and made access to the apartment to search for additional victims.They noted fire venting from the first floor Charlie/Delta apartment (Apt. T-2) out of the sliding glass doors progressing upwards towards the balcony on the second floor.
 
Upon entering the apartment, they conducted a primary search and noted minimal heat with light smoke conditions.The crew accessed the hallway via the apartment entry door and noticed an increase in the temperature and the amount of smoke.They immediately closed the door and exited the apartment via the ground ladder.Upon exiting the apartment, E-1’s crew observed E-292 on the scene with a hand line extending into the apartment of origin, (first floor, Charlie/Delta side, Apt. T-2).
 
The officer on E-1 noted white smoke coming from the unit.Having already laid a supply line from the intersection of the alley and Deanwood Road, E-292’s crew extended a 1 ¾” hand line into the apartment of origin. Moderate fire conditions with zero visibility were encountered, and they reported feeling a great deal of heat on their knees as they crawled through the apartment.The Lieutenant and the Firefighter from Truck-1 entered Apartment A-2 via a second floor bedroom window (Alpha/Delta side) and began a search for additional victims. As they traversed the living room area they found an unconscious male resident (victim #2).
 
At 1836 hours, the Lieutenant notified Command via an urgent transmission that a victim had been located and they needed assistance with evacuation. The Lieutenant and Firefighter noted a small fire in the rear corner near the victim as they exited the room. The crew returned to the bedroom from which they had entered and closed the door behind them. Victim #2 was then evacuated from the apartment via a ground ladder through the bedroom window, and transferred to EMS personnel on side Alpha.
 
Figure 019 Flame extension and suppression efforts at the rear of the structure. Flames caused the second level glass slider to fail and ignite plastic curtains in the doorway located
 

Figure 019

 
 

The middle level apartment (A2) entrance door was opened by a second search crew around the same time as the second couch ignited, creating a ventilation flow path from the second floor balcony, through the apartment, and upwards into the stairwell (third floor). This flow path follows the same general route through the apartment and into the stairwell as was seen in the terrace level apartment below. Squad 303’s crew arrived on scene after the bulk of the fire in the terrace level apartment had been suppressed and appeared to be under control. The crew entered the front stairwell, which had minimal smoke up to the second level and the crew began to systematically search the building.

Squad 303’s crew proceeded to search two apartments before entering the third floor right side apartment to conduct a search, leaving the entrance door open. It should also be noted that carpeting impacted the bottom of the door and prevented the apartment entrance doors on the second and third levels from closing automatically. The entry doors had to be actively pushed closed to overcome the friction of the carpet.

 

Photo depicting building smoke and fire conditions around the arrival of Squad 303.

Note the lack of heavy smoke or fire in the stairwell or terrace level.

There is also no indication of the growing fire in the second (middle) level apartment.

 

 

 

When Squad 303’s crew of two firefighters entered the third level apartment (B2), smoke was banked about halfway down the walls with moderate visibility. The crew could clearly see the floor of the apartment without the need to crawl below the smoke layer to search. Squad 303’s crew was unaware of the flames spreading across the two couches in the second floor apartment below them. The crew split in order to search the apartment faster, with one firefighter searching the front bedrooms and the officer searching the kitchen and living room.

As flames in the second level began to rollover into the apartment entranceway, the smoke layer in the third level quickly dropped to the floor with a rapid increase in temperature. With Squad 303’s crew searching above, flames began to extend into the stairwell, supplied by sufficient ventilation flowing through the apartment. This combination of fuel, heat and oxygen rich fresh air resulted in a rapid increase in heat release rate and flashover of the second level apartment followed by full room involvement.

The open entrance doors on the second and third levels created a ventilation flow path through the second floor apartment, into the sealed stairwell and up through the third floor apartment directly above. The flames followed this flow path and extended from the second floor, through the stairwell and into the living room area of the third floor apartment. Flashover of the third floor occurred approximately 30 seconds after the second floor experienced flashover.

Figure 026 and 027

 

Rollover from the second level apartment into the stairwell.

 

 
 
Flames followed the ventilation flow path and extend into the third floor apartment, resulting in ignition of the couches just inside the doorway.

 

 

    

 

Command sounded the building evacuation tones as flames extended into the hallway and up to the third level apartment.

Two couches just inside the entrance door on the third level ignited, blocking the primary means of egress for both firefighters from Squad 303. Upon hearing the evacuation horns from the trucks, the second firefighter from Squad 303 (searching the front bedrooms) attempted to exit the apartment via the apartment entrance door, however he was blocked by flames in the living room and stairwell.

Trapped in the bedroom, the firefighter bailed out headfirst down a ground ladder on the front side from the third floor. Squad 303 officer’s means of egress through the apartment entrance door was also blocked by the flames in the living room and stairwell. There were no windows located in the rear of the apartment.

The only means of escape was the balcony slider, however the entire balcony was engulfed in flames from the fully involved apartment below. With both escape routes blocked by flames and experiencing extremely high heat conditions, Squad 303’s officer requested assistance and declared a MAYDAY from the rear of the third floor apartment.

Firefighters re-entered the structure to combat the fire and locate the trapped firefighter. The downed firefighter was eventually located on the third level just inside the sliding glass door and was removed to the rear balcony. The firefighter was then extricated in a stokes rescue basket down the aerial ladder of a truck located in the rear, where he was subsequently transported to the hospital.

Effects of Compartmentation on Fire Spread

The Post Incident Analysis Team requested that alternate modeling scenarios be conducted to explore the effects of compartmentation on fire spread throughout the building.

The team specifically wanted to know how the ventilation flow paths through the stairwell would differ if the second or third level apartment entry doors were shut after entering/leaving the apartments. Two alternate computer fire modeling scenarios were conducted.

The first alternative modeling run featured the exact same fire scenario, except the second (middle) level apartment door was closed after the last victim was removed from that apartment. The apartment entry doors from the stairwell were fire-rated doors constructed of solid wood.

  • As soon as the door is shut, the ventilation flow path through the apartment and up the stairwell is blocked.

 

Shutting the second level apartment door blocks the flow path and flame extension into the stairwell. 

Even with the third floor apartment door left open, the model indicates that the stairwell and third floor remain tenable for firefighters. Flames eventually extend from the third floor balcony into the apartment, however the escape routes through the stairwell and the front apartment windows are accessible.           

The model indicates that closing the second level apartment door prevents the flow of smoke, heat and other products of combustion from entering the stairwell, thus preventing flashover of the stairwell and the third level. As long as the second floor entry door remains shut, the model indicated that the conditions within the stairwell and third floor remain tenable for firefighters, even with the third floor apartment door open.

A second alternative modeling scenario was conducted where the third level entrance door was closed after crews made entry to search the apartment.The same fire conditions from the actual model were used.When the door remained closed, the outlet of the ventilation flow path was blocked at the top of the stairs. Without a complete flow path, there wasn’t sufficient oxygen flowing through the second floor apartment to support extended burning in the stairwell.

Consequently after flashover of the second floor, the flames in the stairwell only exist momentarily before consuming all available oxygen and becoming ventilation limited.The fire model indicated that temperatures within the third floor apartment stayed tenable for firefighters, even with a fully developed fire on the second floor and flames in the stairwell.

Flames would eventually extend up the rear balcony to the third level, however they would not block egress through the living room and front windows of the apartment.By closing the apartment door on the third floor and blocking the outlet for fire gases emanating from the second floor apartment, the third floor apartment remains tenable for firefighting crews and the temperatures only briefly spike in the stairwell before the fire becomes ventilation limited.The ventilation flow through the apartments results in an increased burning rate within both the second and third levels, as well as the stairwell.                     

Results of each modeling scenario describing extent of flame spread

Results of each modeling scenario describing extent of flame spread.

 
 
 
 
 
 
 
 
 
 
The Effects of Compartmentation on Fire Damage to the StructureThe impact of compartmentation on fire and smoke spread is evident by examining the post-fire damage throughout the structure. While other factors contributed to the relative fire damage, including fire department overhaul and relative apartment configuration, analyzing the damage to the building and the position of the apartment entry doors provides insight on the benefits of compartmentation.

By closing apartment unit entrance doors and interior hollow core doors, one can slow or even block the ventilation flow path through the structure, thus significantly reducing the rate of fire spread. The photos below represent the post-fire damage in all six apartments within the fire building. Four of the six apartment entry doors were open for the majority of the fire and the relative difference in damage is clearly evident.

Terrace level stairwell landing looking into T1 (left) and T2 (right) apartments.

 

Door Closed……Door Open

 

 

Using doors to compartmentalize and limit fire and smoke spread in a structure is not limited to fire-rated entrance doors. Interior hollow core doors also offer considerable protection for compartmentation purposes.

A search crew utilizing the Vent, Enter and Search (VES) technique through a front window used a hollow core bedroom door to isolate themselves from the developing fire in the living room of apartment A2.

As the crews removed the second victim from the living room to the bedroom, they shut the bedroom hollow core door behind them.

The living room soon experienced flashover followed by full room involvement, however the bedroom remained isolated from the heat and smoke for the duration of the fire. The photos below illustrate this effective use of compartmentation to protect firefighters during a search.

 
Controling the Doors during VES

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
SUMMARY:
While no fire model will exactly replicate a fire, this model provided insight on the route of fire spread, the rapid fire growth leading to flashover of the second and third level, and the benefits of compartmentation on slowing fire and smoke spread.
  • The unidirectional flow path up the stairs from the terrace level apartment resulted in a high rate of convective heat transfer to the firefighters initially attempting to descend the stairs, making attacking the seat of the fire very difficult.
  • The model then supported the fact that the main stairwell acted as an open channel for fire and smoke spread between the second and third levels, resulting in flashover of the third level in approximately 30 seconds after the second level.
  • This rapid fire growth leading to flashover is supported by photographs, witness statements and fireground audio.
  • The model was then utilized to explore the effects of compartmentation using apartment entrance doors.
  • The FDS model supported the scene observations and indicated that shutting the entrance doors blocked the flow of buoyancy driven fire gases through the structure, ultimately preventing fire extension to the third floor apartment via the stairwell.
  • The FDS model was utilized as part of the overall engineering analysis of this tragic fire and allowed for a better understanding of the events that led to the firefighter MAYDAY and subsequent Line of Duty Death.
  • The model was also used as an educational tool providing insight on potential methods of preventing similar tragedies in the future.
  • The results of this engineering analysis are intended to be reviewed by the Post Incident Analysis Team to assist in the creation of recommendations to mitigate the danger associated with future fire incidents.

References:

Fire/EMS Safety, Health and Survival Week 2011, Days One thru Seven;Training and Preparedness

No comments

Did you remember to participate in the 2011 Fire/EMS Safety, Health and Survival Week?

The International Association of Fire Chiefs (IAFC) and the International Association of Fire Fighters(IAFF) were formative in developing this year’s  2011 Fire/EMS Safety, Health and Survival Week (also known as Safety Week)which commences today, June 19th and ends on June 25th. ( Week of June 19-25, 2011)

The message this year is: Surviving the Fire Ground – Fire Fighter, Fire Officer and Command Preparedness

Safety, Health and Survival Week (Safety Week) is a collaborative program sponsored by the IAFC and the IAFF, coordinated by the IAFC’s Safety, Health and Survival Section and the IAFF’s Division of Occupational Health, Safety and Medicine, in partnership with more than 20 national fire and emergency service organizations.

We’ve got a whole lot of resources, links and daily commentary and articles that were posted on each day of SAfety Week over at CommandSafety.com

If you didn’t have a look and read, take some time to do so. If you didn’t do anything during Safety Week, there’s always next week or the week after… find the time and commit to some training, insights, dialog, discussion…Get Prepared.

Day One: Fire/EMS Safety, Health & Survival Week 2011: Day One- Are You Ready?

Day Two: Fire/EMS Safety, Health and Survival Week: Day Two- Building Knowledge = Fire Fighter Safety

Day Three: Fire/EMS Safety, Health and Survival Week: Day Three-The New Rules of Engagement

Day Four: Fire/EMS Safety, Health and Survival Week: Day Four -The New Fire Ground

Day Five: Fire/EMS Safety, Health and Survival Week 2011: Day Five: Near-Misses, Maydays and Floor Collapses

Day Six: Fire/EMS Safety, Health and Survival Week 2011, Day Six; From Waldbaum’s to Hackensack-Worcester to Charleston; Legacies for Operational Safety

Day Seven: Fire/EMS Safety, Health and Survival Week 2011, Day Seven; Fire Fighter, Fire Officer and Command Training and Preparedness

SFFD Firefighter Memorials and Updates

No comments

More details emerged Monday about last week’s fatal Diamond Heights blaze, as fire officials said an emergency alert accidentally went off on a nearby fire engine about the same time two firefighters’ personal alarms sounded inside the burning building according to published reports.

Lt. Vincent Perez, 48, and firefighter-paramedic Anthony Valerio, 53, of Engine Company 26 both died from injuries they suffered while battling a blaze at a four-story home at 133 Berkeley Way on Thursday morning.

While fighting the fire, one or both of Valerio and Perez’s personal alert safety system devices went off.  Around the same time, a firefighter on Engine Company 20 — which had yet to arrive on the scene — had inadvertently hit the emergency button on the engine.

Firefighter memorials

A joint funeral for fire Lt. Vincent Perez and firefighter-paramedic Anthony Valerio will be held at 12:30 p.m. Friday at St. Mary’s Cathedral, 1111 Gough St. in San Francisco. A vigil for the two men will be held at 7 p.m. Thursday, also at St. Mary’s.

San Francisco Fire Fighters Local 798 has established trust accounts at the San Francisco Fire Credit Union for the families of Perez and Valerio. Donations can be made to SFFCU, 3201 California St., San Francisco, CA 94118.

Condolence messages can be sent to Fire Station 26, 80 Digby St., San Francisco, CA 94131.

San Francisco FD mourns the loss of a Second Firefighter LODD After Diamond Heights Fire

No comments



SFFD Firefighter Anthony Valerio

It’s being reported that San Francisco Fire Fighter Anthony Valerio passed away this morning as a result of injuries sustained while operating the Diamond Heights fire on Thursday June 2nd. This becomes the second line of duty death from this incident that also resulted in the LODD of Lt. Vincent Perez. Anthony “Tony” Valerio, a 53-year-old firefighter and paramedic critically injured in the Thursday blaze, died at San Francisco General Hospital at about 7:40 a.m., city officials said.

Read more: http://www.sfgate.com/cgi-bin/article.cgi?f=/c/a/2011/06/04/BA2F1JPNS2.DTL#ixzz1OKjGjnNs

San Francisco firefighter Anthony Valerio is the second firefighter to die from Thursday’s Diamond Heights fire. According to San Francisco Fire Chief Joanne Hayes-White, Valerio had “significant damage to his respiratory system” and burns across his body after Thursday’s fire. Valerio has burns to 12 percent of his body.

WKGO TV ABC7 reports that according to San Francisco Fire Deputy Chief Mike Gardner said most of Fire Fighter Valerio’s burns were from steam and not from fire, adding that the temperature inside the structure was between 500 and 700 degrees.

Previous Coverage, HERE, HERE and HERE

  • Logs show desperate hunt for doomed SF firefighters, HERE
  • 

Read more: http://www.sfgate.com/cgi-bin/article.cgi?f=/c/a/2011/06/03/BAJG1JPBKV.DTL#ixzz1OKn7vgot

Updated Sunday June 5

  

San Francisco’s fire chief says this is the first time in her 21 years with the department that two firefighters have died in the same fire.

Slowly and silently, Valerio’s body was wheeled to an awaiting van; the silence finally broken by the rain and his family’s tears. The pain hung in the air outside San Francisco General Hospital – a place that became a gathering spot for the hopeful. Valerio’s family and friends had been there around the clock since Thursday. Valerio and Perez were rushed to the hospital after the two were found unresponsive inside a burning house in Diamond Heights – a sudden blast knocked them down. Perez died late Thursday. From Reports published by WKGO-TV ABC 7 ; “It is particularly difficult, you’re mourning the loss of one and then to have another one very close from the same fire is challenging,” said San Francisco Fire Chief Joanne Hayes-White.

Saturday was the first time Valerio’s doctors gave details about the uphill battle the 53-year-old faced – including the fact that he was in cardiac arrest the moment he arrived at SF General.

“Between all the injuries he had from the initial blast, the smoke inhalation, the fact that he had a really bad lung injury, which was precipitated by what happened on the scene, but we try to do everything we can,” said SF General Hospital Dr. Andre Campbell.

But in the end it wasn’t enough. On this day, the firefighter’s two families, his work family at Station 26 and his immediate family – realized Valerio’s 40 hour long fight to survive was over.

The fire department and the families have agreed to have a joint funeral for both Tony Valerio and Lt. Perez on Friday at Saint Mary’s Cathedral.

Lt. Vincent Perez, San Francisco FD
Firefighter Anthony Valerio  

  

From Thursday

Previous postings from Commandsafety.com;

Courtesy Patty Stanton

Courtesy Patty Stanton

Courtesy Patty Stanton

Updates from San Francisco;

Charlie Side

Charlie Side, Fire Extending

Alpha Street Side from Google Streets

Aerial Charlie Side

Coincidentially, we posted a remembrance to the DCFD Cherry Road Townhouse Fire and Double FireFighter LODD from May, 1999 that is worth another look as it has similar connotations related to fire behavior, flashover conditions and multiple floor level construction factors during initial fire suppression operations, HERE

Tactical Patience and New Considerations of Ventilation on Fire Behavior in Legacy and Contemporary Residential Construction

1 comment

Tactical Patience and the New Considerations of Ventilation on Fire Behavior in Legacy and Contemporary Residential Construction

UL Ventilation and Fire Behavior Full Scale Testing

 

Impact of Ventilation on Fire Behavior in Legacy and Contemporary Residential Construction

For many of you that have been following my writings and perspectives on building construction, firefighting, command risk management and operational excellence for firefighter safety have long recognized that I have been promoting and advocating the fact the fireground is changining, our stratgies and tactics demand change adn does the demand for increased knowledge within the areas of building construction, fire dynamics, while integrating the art and science of firefighting. The most recent release of the testing report from Underwriters Laboratories; Impact of Ventilation on Fire Behavior in Legacy and Contemporary Residential Construction and the accompaning emphirical data further validates assumptions and presmises that many of us shared based upon field obervations and first hand incident operations related to the dramatic changes being witnessed as a result of operational challenges in a wide varity of occupanies and building types.

This material is a must read for all emerging and practicing company and command officers ( for starters) to being grasping the magnitude and extent of quantifiable data that supports the premise that combat fire engagement and suppression operations and the rules of engagement are going to change and that change is fast approaching.

 Considerations for Tactical Patience and Adaptive Fireground Management are continued themes I will expand upon in future postings….

Here’s the executive summary of the report and findings from UL. For an download of the entire UL Report, go HERE.

Under the United States Department of Homeland Security (DHS) Assistance to Firefighter Grant Program, Underwriters Laboratories examined fire service ventilation practices as well as the impact of changes in modern house geometries.  There has been a steady change in the residential fire environment over the past several decades.  These changes include larger homes, more open floor plans and volumes and increased synthetic fuel loads.  This series of experiments examine this change in fire behavior and the impact on firefighter ventilation tactics.  This fire research project developed the empirical data that is needed to quantify the fire behavior associated with these scenarios and result in immediately developing the necessary firefighting ventilation practices to reduce firefighter death and injury.

Two houses were constructed in the large fire facility of Underwriters Laboratories in Northbrook, IL.  The first of two houses constructed was a one-story, 1200 ft2, 3 bedroom, 1 bathroom house with 8 total rooms.  The second house was a two-story 3200 ft2, 4 bedroom, 2.5 bathroom house with 12 total rooms.  The second house featured a modern open floor plan, two-story great room and open foyer.   Fifteen experiments were conducted varying the ventilation locations and the number of ventilation openings.  Ventilation scenarios included ventilating the front door only, opening the front door and a window near and remote from the seat of the fire, opening a window only and ventilating a higher opening in the two-story house.  One scenario in each house was conducted in triplicate to examine repeatability.

The results of these experiments provide knowledge for the fire service for them to examine their thought processes, standard operating procedures and training content.  Several tactical considerations were developed utilizing the data from the experiments to provide specific examples of changes that can be adopted based on a departments current strategies and tactics.

Under the United States Department of Homeland Security (DHS) Assistance to Firefighter Grant Program, Underwriters Laboratories examined fire service ventilation practices as well as the impact of changes in modern house geometries.

There has been a steady change in the residential fire environment over the past several decades. These changes include larger homes, more open floor plans and volumes and increased synthetic fuel loads. This series of experiments examine this change in fire behavior and the impact on firefighter ventilation tactics.

This fire research project developed the empirical data that is needed to quantify the fire behavior associated with these scenarios and result in immediately developing the necessary firefighting ventilation practices to reduce firefighter death and injury.

  • Two houses were constructed in the large fire facility of Underwriters Laboratories in Northbrook, IL.
  • The first of two houses constructed was a one-story, 1200 ft2, 3 bedroom, 1 bathroom house with 8 total rooms.
  • The second house was a two-story 3200 ft2, 4 bedroom, and 2.5 bathroom house with 12 total rooms.
  • The second house featured a modern open floor plan, two story great room and open foyer.

 Fifteen experiments were conducted varying the ventilation locations and the number of ventilation openings. Ventilation scenarios included ventilating the front door only, opening the front door and a window near and remote from the seat of the fire, opening a window only and ventilating a higher opening in the two-story house.

One scenario in each house was conducted in triplicate to examine repeatability. The results of these experiments provide knowledge for the fire service for them to examine their thought processes, standard operating procedures and training content. Several tactical considerations were developed utilizing the data from the experiments to provide specific examples of changes that can be adopted based on a departments current strategies and tactics.

The tactical considerations addressed include:

  • Stages of fire development: The stages of fire development change when a fire becomes ventilation limited.
    • It is common with today’s fire environment to have a decay period prior to flashover which emphasizes the importance of ventilatio
  • Forcing the front door is ventilation: Forcing entry has to be thought of as ventilation as well.
    • While forcing entry is necessary to fight the fire it must also trigger the thought that air is being fed to the fire and the clock is ticking before either the fire gets extinguished or it grows until an untenable condition exists jeopardizing the safety of everyone in the structure.
  • No smoke showing: A common event during the experiments was that once the fire became ventilation limited the smoke being forced out of the gaps of the houses greatly diminished or stopped all together.
    • No some showing during size-up should increase awareness of the potential conditions inside.
  • Coordination: If you add air to the fire and don’t apply water in the appropriate time frame the fire gets larger and safety decreases.
    • Examining the times to untenability gives the best case scenario of how coordinated the attack needs to be.
    • Taking the average time for every experiment from the time of ventilation to the time of the onset of firefighter untenability conditions yields 100 seconds for the one-story house and 200 seconds for the two-story house
    • In many of the experiments from the onset of firefighter untenability until flashover was less than 10 seconds.
    • These times should be treated as being very conservative. If a vent location already exists because the homeowner left a window or door open then the fire is going to respond faster to additional ventilation opening because the temperatures in the house are going to be higher.
    • Coordination of fire attack crew is essential for a positive outcome in today’s fire environment.
  • Smoke tunneling and rapid air movement through the front door: Once the front door is opened attention should be given to the flow through the front door.
    • A rapid in rush of air or a tunneling effect could indicate a ventilation limited fire.
  • Vent Enter Search (VES): During a VES operation, primary importance should be given to closing the door to the room.
    • This eliminates the impact of the open vent and increases tenability for potential occupants and firefighters while the smoke ventilates from the now isolated room.
  • Flow paths: Every new ventilation opening provides a new flow path to the fire and vice versa.
    • This could create very dangerous conditions when there is a ventilation limited fire.
  • Can you vent enough?: In the experiments where multiple ventilation locations were made it was not possible to create fuel limited fires.
    • The fire responded to all the additional air provided.
    • That means that even with a ventilation location open the fire is still ventilation limited and will respond just as fast or faster to any additional air.
    • It is more likely that the fire will respond faster because the already open ventilation location is allowing the fire to maintain a higher temperature than if everything was closed. In these cases rapid fire progression if highly probable and coordination of fire attack with ventilation is paramount.
  • Impact of shut door on occupant tenability and firefighter tenability: Conditions in every experiment for the closed bedroom remained tenable for temperature and oxygen concentration thresholds.
    • This means that the act of closing a door between the occupant and the fire or a firefighter and the fire can increase the chance of survivability.
    • During firefighter operations if a firefighter is searching ahead of a hoseline or becomes separated from his crew and conditions deteriorate then a good choice of actions would be to get in a room with a closed door until the fire is knocked down or escape out of the room’s window with more time provided by the closed door
  • Potential impact of open vent already on flashover time: All of these experiments were designed to examine the first ventilation actions by an arriving crew when there are no ventilation openings.
    • It is possible that the fire will fail a window prior to fire department arrival or that a door or window was left open by the occupant while exiting.
    • It is important to understand that an already open ventilation location is providing air to the fire, allowing it to sustain or grow.
  • Pushing fire: There were no temperature spikes in any of the rooms, especially the rooms adjacent to the fire room when water was applied from the outside. It appears that in most cases the fire was slowed down by the water application and that external water application had no negative impacts to occupant survivability.
    • While the fog stream “pushed” steam along the flow path there was no fire “pushed”.
  • No damage to surrounding rooms: Just as the fire triangle depicts, fire needs oxygen to burn.
    • A condition that existed in every experiment was that the fire (living room or family room) grew until oxygen was reduced below levels to sustain it.
    • This means that it decreased the oxygen in the entire house by lowering the oxygen in surrounding rooms and the more remote bedrooms until combustion was not possible.
    • In most cases surrounding rooms such as the dining room and kitchen had no fire in them even when the fire room was fully involved in flames and was ventilating out of the structure.

Online Training Program

In order to make the results of this study more user friendly for the fire service to examine, UL developed an online interactive training module that can be viewed by clicking here.  The program includes a professionally narrated description of all of the experiments, their results and the tactical considerations.  Experimental video is used and graphical data is explained in a way that brings science to the street level firefighter.

UL University On-Line CBT

 

Comparison of Modern and Legacy Home Furnishings

An experiment was conducted with two side by side living room fires.   The purpose was to gain knowledge on the difference between modern and legacy furnishings.  The rooms measured 12 ft by 12 ft, with an 8 ft ceiling and had an 8 ft wide by 7 ft tall opening on the front wall.  Both rooms contained similar amounts of like furnishings.

The modern room was lined with a layer of ½ inch painted gypsum board and the floor was covered with carpet and padding.

  • The furnishings included a microfiber covered polyurethane foam filled sectional sofa, engineered wood coffee table, end table, television stand and book case.
  • The sofa had a polyester throw placed on its right side.  The end table had a lamp with polyester shade on top of it and a wicker basket inside it.
  • The coffee table had six color magazines, a television remote and a synthetic plant on it.
  • The television stand had a color magazine and a 37 inch flat panel television.
  • The book case had two small plastic bins, two picture frames and two glass vases on it.
  • The right rear corner of the room had a plastic toy bin, a plastic toy tub and four stuffed toys.
  • The rear wall had polyester curtains hanging from a metal rod and the side walls had wood framed pictures hung on them.

The legacy room was lined with a layer of ½ inch painted cement board and the floor was covered with unfinished hardwood flooring.

  • The furnishings included a cotton covered, cotton batting filled sectional sofa, solid wood coffee table, two end tables, and television stand.
  • The sofa had a cotton throw placed on its right side.
  • Both end tables had a lamp with polyester shade on top of them.
  • The one on the left side of the sofa had two paperback books on it.
  • A wicker basket was located on the floor in front of the right side of the sofa at the floor level.
  • The coffee table had three hard-covered books, a television remote and a synthetic plant on it.
  • The television stand had a 27 inch tube television.
  • The right front corner of the room had a wood toy bin, and multiple wood toys.
  • The rear wall had cotton curtains hanging from a metal rod and the side walls had wood framed pictures hung on them.

Both rooms were ignited by placing a lit stick candle on the right side of the sofa.  The fires were allowed to grow until flashover.  The modern room transitioned to flashover in 3 minutes and 30 seconds and the legacy room at 29 minutes and 30 seconds.

View the entire video, or you may also download the video:

First-Due Arriving Companies; Are You Prepared?

No comments

As the First-Due Fire Company; Officer and crew, Are you prepared to address the fireground variables and occupancy risks upon your arrival and during the initial stages of your deployment and operations? Are you combat ready or passively engaged?  

It seems we’ve struck some interests over past week since we first discussed the First-Due Fire Officer  on the most recent edition of Taking it to the StreetsTM where we had a vibrant and insightful program in which we discussion some of the expansive facets related to the First-Due Fire Officer.     

 The First-Due Fire Office program can be downloaded HERE at Firefighter Netcast.com   

The formulative discussion revolved around a variety of functional elements, traits, responsibilities and duties befalling the First-Due Officer, and was followed up with a post here on Thecompanyoffer.com. We discussed how today’s First-Due Officer must perform smarter with increased perceptions, discernments and acumens with intelligence and wisdom that is drawn from further progressing and collective fire ground response and operational experiences.   

My good friend Captain Willie Wines (aka The Iron Fireman) posted a great follow-up article associated with the radio program on his blog associated with further interpretations of the First-Due Officer. Check out “The First-Due Officer; What are you thinking?”  HERE.   

To further our dialog on the first-due, I’ve added a few series of video clips and images with related links to promote and stimulate your view of the first-due fireground scene as it relates to the variables and personnel perceptions; the need for diligence and cognitive situational awareness and risk assessment and being truly “prepared” both mentally and physically. By way of physically, I mean- is your gear and PPE, functional, operational and adequately in-place?   

  As you can see there are numerous instances where the difference in the incident outcome correlated to the level of PPE protection that was in-place and implemented at the time of adverse conditions or unexpected or unforeseen circumstances.   

 Here’s today’s situations to think about at the station, around the kitchen table, over a cup of coffee in the day room after your next alarm or tonight at the station for a “back step” company drill.    

  • What are the Adverse Conditions that might be encounted upon arrival as the First-Due?
  • Flashover, Backdraft, Compromised or degraded Structural Conditions, Collapsed Conditions, Structural Collapse, Wind Drive Fire Behavior, Extreme Fire Behavior, Pre-Flashover/ Post-Flashover….
  • How Effective are you in Reading the Smoke?
  • How About Reading the Building? Do you understand Occupancy Profiling and Occupancy Risk?
  • Are you Taking the Time to Read the Subtle or Pronounced Fireground Indicators.; Comprehend their meaning or are you just “too engaged in the tactic or task?”
  • Do you have an appreciation for Tactical Patience?
  • Are your operations Tactically Driven by SOP’s and SOGs?
  • What Rules of Engagment are you considering?
  • Have and IAP in mind?
 YouTube Preview Image   

 There have been a lot of articles and postings on adverse conditions as companies are opening up or pushing into the structure on the initial entry. Take a look at the next two series of video clips related to flashover conditions and the impact of that fire behavior on the companies and personnel. In each instance companies were extremely fortunate that the injuries sustained were not more severe than encountered.  

  • What encounters have you or your company experienced?
  • In retrospect how effective was the initial risk assessment and occupancy profile-was the size-up appropriate or were key indicators missed or neglected?
  • Did the fast pace of the initial arrival and subsequent deployment filter or obscure mission critical indicators that should have been identified and acted upon?  
  • Did the tactical assignment and task overshadow tactical patience?
  • Did someone or everyone miss reading the smoke, fire or occupancy risk?
  • Did other tactical assignments contribute toward the unexpected or adverse conditions encountered, such as ventilation induced flashover? ( More on that topic for a later post; See Taking it the Streets November 4, 2010 show

          

Firefighter Will Gregory exits the home with his PPE on fire. Photo by Brian Haney, The Daily Record.

There are a series of photos  from a previous posting at STATter911 HERE that depicts firefighers working to push-in on a fire in a small residential occupancy. The ensuing flashover ignites the PPE of one firefighter. Look at the series of photographs and  take note of the fire and smoke conditions, the size and profile of the occupancy ( remember it’s Occupancy RISK not Occupancy Type).   

  • Think about the sequencing of your initial operations.
  • Think about the mission critical 360;
  • how does that play into your initial incident actions plan (IAP)?

   

The Dynamics of the Fireground in Seconds

Companies were dispatched for an assignment for a house fire. Both E807 and TK807 responded with crews of 4 personnel each. E813 arrived on the scene and reported light smoke showing on side Alpha. Upon arrival on the scene, the crew from TK807 (four staff) made entry to the house. The following series of events led to conditions in the house that presented a flashover environment. The hose line from E813 burst, a backup line was not charged due to no established water supply, and the house was not yet ventilated. Without the protection of a hose line, the crew was committed to the house when the room flashed. One firefighter was apparently far enough in the house to avoid any injury, A second FF received 2nd degree burns to his right shoulder, and a third FF received the full force of the flashover suffering second-third degree burns to his face, hands, and the majority of his torso. (Original incident information posted at the time of the event)   

  •  Photo 1: Firefighters don PPE and SCBA with light smoke visible in this first of four pictures shot by Tony George of PGFD Station 813  
  •  Photo 2: Six seconds later a small amount of fire and darker smoke can be seen at the sliding glass door. 
  •  Photo3: Forty-eight seconds after the initial picture, more fire and darker smoke are apparent. 
  •  Photo 4: Exactly two-minutes after the first picture was shot, flashover occurs with firefighters inside. 

For a complete narrative and futher incident details of this previous STATter911 postings related to this event go HERE, and HERE  

Take a good look at the performance of PPE when utilized and implemented correctly…. 

Don’t ever underestimate the dynamics and uncertainty of the evolving fireground during your operations. The video clip here depicts how quickly operations can change from an investigation to a major mass casualty incident.

For a comprehensive look at this event go here are two links for you to visit, HERE at Commandsafety.com and the NIOSH Report HERE

     

Be prepared for the unexpected and always use extreme caution and heightened situational awareness and fluid risk assessment and reconnaissance processing to stay atop of any undefined and evolving incident. Do not allow the potential lack of severity; of what may have all the indications of an unremarkable/uneventful and common call run such as a gas odor investigation or a natural gas leak cause your companies to have less than a high level of alert, focus and attentive accretions through all phases and deployments of the incident. Don’t become complacent.

In addition, take a look at some information relate to another tragic incident response to a reported gas leak that occurred in December, 1983 that lead to five fire fighter LODD’s in Buffalo, New York. HERE 

  • Archived Report From STATter911, from May, 2009 HERE and recent 2010 update HERE with fireground Audio
  • Prince George’s County (MD) Fire Press Release from May 7, 2009, HERE
  • Slide Show from WUSA9.com HERE 
  • BING mapping Images, HERE

  Here’s a series of Reports worth your time to read related to the First-Due:

  • City of Charleston Post Incident Assessment and Review Team Phase I Report, HERE
  • Routley Final Phase II Report HERE
  • NIOSH Investigative Report, HERE
  • Fire Fighting Tactics Under Wind Driven Conditions Report, HERE
  • Reference Data HERE
  • The report is also available for download at the NIST, HERE
  • Synopsis HERE
  • Report: Trends in Firefighter Fatalities Due to Structural Collapse1979-2002
  • Colerain Township (OH) Fire and EMS Department Final Report Investigation Analysis of the Squirrels Nest Lane Firefighter Line of Duty Deaths Incident Overview, HERE; NIOSH Report, HERE; Investigative Report, HERE
  • Rowhouse Fire Close Call- Fire Behavior Acting Badly

    No comments

    httpv://www.youtube.com/watch?v=M00Vl7cxuYo

    Five Baltimore  City (MD) firefighters were hurt as a powerful fire ball engulfed the front of the dwelling. One firefighter was hospitalized and is reported in stable condition. Two other firefighterrs were hurt during overhaul. The fire in a rowhouse was being worked by companies, when conditions rapidly changed resulting in the extreme fire behavior.

    • As a company or command officer are you maintaining a keen level of situational awareness of fire conditions and observing and predicting fire behavior?
    • When fire behaves badly, there may be little time to react and overcome the severity and magnitude of those self-revealing conditions in a timely manner to preclude injury.
    • Are you monitoring conditions based upon tactical actions and tasks?
    • According to published reports, the early morning fire began in the basement and quickly traveled to the first floor.

     