Fire Dynamics Simulation of 2011 Baltimore County LODD- 30 Dowling Circle

No comments

Operations at 30 Dowling Circle 01.19.2011 Box 11-09

 On Wednesday, January 19, 2011, a fire occurred in an apartment building located in the Hillendale section of Baltimore County, Maryland. This fire resulted in the line of duty death (LODD) of volunteer firefighter Mark G. Falkenhan, who was operating as the acting lieutenant on Squad 303 . Upon their arrival, FF Falkenhan and a second firefighter from Squad 303 deployed to the upper floors of the apartment building to conduct search and rescue operations. Other fire department units were already involved with both firefighting operations and effecting rescues of trapped civilians.

During these operations, FF Falkenhan and his partner became trapped in a third floor apartment by rapidly spreading fire and smoke conditions. The second firefighter was able to self-egress the building by diving headfirst down a ladder on the front (address side) of the building. FF Falkenhan declared a “MAYDAY” and implemented “MAYDAY” procedures, but was unable to escape or be rescued.

FF Falkenhan was located and removed via a balcony on the third floor in the rear of the building. Resuscitative efforts began immediately upon removal from the balcony, and continued en route to the hospital. FF Falkenhan succumbed to his injuries and was pronounced deceased at the hospital.

Mark Gray Falkenhan had dedicated his life to serving others. He perished in the line of duty on January 19, 2011 while performing search and rescue operations at a multi-alarm apartment fire in Hillendale, Baltimore County (Maryland). He was 43 years old.

 

Firefighter Mark Falkenhan

30 Dowling Circle

 

The Baltimore County (MD) Fire Department published the Line of Duty Death Investgation Report of the 30 Dowling Circle Fire recently.

The report was written by a Line of Duty Death Investigation Team comprised of departmental members, including representatives of the local firefighters’ union and the Baltimore County Volunteer Firemen’s Association.

An overview and executive narrative of the final report (PDF) on the apartment fire where Volunteer Firefighter Mark Falkenhan sustained fatal injuries was posed on CommandSafety.com HERE.

FF Mark Falkenhan

 On Wednesday, January 19, 2011, a fire occurred in an apartment building located in the Hillendale section of Baltimore County, Maryland. This fire resulted in the line of duty death (LODD) of volunteer firefighter Mark G. Falkenhan, who was operating as the acting lieutenant on Squad 303 (for purposes of this report, Mark will be referred to as FF Falkenhan).

Upon their arrival, FF Falkenhan and a second firefighter (FF # 2) from Squad 303 deployed to the upper floors of the apartment building to conduct search and rescue operations. Other fire department units were already involved with both firefighting operations and effecting rescues of trapped civilians.

During these operations, FF Falkenhan and FF # 2 became trapped in a third floor apartment by rapidly spreading fire and smoke conditions. FF # 2 was able to self-egress the building by diving headfirst down a ladder on the front (address side) of the building. FF Falkenhan declared a “MAYDAY” and implemented “MAYDAY” procedures, but was unable to escape or be rescued.

FF Falkenhan was located and removed via a balcony on the third floor in the rear of the building. Resuscitative efforts began immediately upon removal from the balcony, and continued en route to the hospital. FF Falkenhan succumbed to his injuries and was pronounced deceased at the hospital.

The investigating team examined any and all data available, including independent analysis of the self contained breathing apparatus (SCBA), turnout gear and autopsy report. The Bureau of Alcohol, Tobacco, Firearms and Explosives (ATF) produced a fire model to assist with evaluating fire behavior. Multiple site inspections were conducted. Extensive interviews were conducted by the team which also attended those conducted by investigators from the National Institute for Occupational Safety and Health (NIOSH). Photographic and audio transcripts were also thoroughly analyzed. A comprehensive timeline of events was developed. All information used to make decisions regarding recommendations was corroborated by at least two sources.

  • In fairness to those units involved in this incident, the investigating team had the advantage of examining this incident over the period of several months. Furthermore, given the size and nature of the event, and the fact that arriving crews were met with serious fire conditions and several residents trapped and in immediate danger, all personnel should be commended for their efforts for performing several rescues which prevented an even greater tragedy.
  • The team did not identify a particular primary reason for FF Falkenhan’s death.
  • What were identified were many secondary issues involving but not limited to crew integrity, incident command, strategy and tactics, and communications.
  • These issues are identified and discussed, and recommendations are made in appropriate sections of the report, as well as in a consolidated format in the Report Appendix.

Some of the issues identified in this report may require some type of change to current practices, policies, procedures or equipment. Most, however, do not. Specifically, the analysis and recommendations regarding Incident Command and Strategy and Tactics show that if current policies and procedures are adhered to, the opportunity for catastrophic problems may be reduced.

  • Mark Falkenhan was a well-respected and experienced firefighter.
  • He died performing his duties during a very complex incident with severe fire conditions and unique fire behavior coupled with the immediate need to perform multiple rescues of victims in imminent danger.
  • It would be easy if one particular failure of the system could be identified as the cause of this tragedy.
  • We could fix it and move on. Unfortunately it is not that simple.
  • No incident is “routine”. Mark’s death and this report reinforce that fact.

On Wednesday, January 19, 2011 at 1816 hours, a call was received at the Baltimore County 911 Center from a female occupant at 30 Dowling Circle in the Hillendale section of Baltimore County. The caller stated that her stove was on fire and the fire was spreading to the surrounding cabinets. Fire box 11-09 was dispatched by Baltimore County Fire Dispatch (Dispatch) at 1818 hours consisting of four engine companies, two truck companies, a floodlight unit, and a battalion chief. All units responded on Talkgroup 1-2.

The location, approximately one mile from the first dispatched engine company, is a three story garden-type apartment complex, with brick construction and a composite shingle, truss supported roof. The fire building contained a total of six apartments divided by a common enclosed stairway in the center with one apartment on the left and one to the right of the stairs.

 

Fire Dynamics Simulation of 2011 Baltimore County LODD- 30 Dowling

Fire Dynamics Analysis and Insights

 

INTRODUCTION:

Assistance from the Bureau of Alcohol, Tobacco, Firearms and Explosives (ATF) Fire Research Laboratory (FRL) was requested for a fire at 30 Dowling Circle by the Baltimore County Fire Investigation Division (FID) through the ATF Baltimore Field Division on the night of January 19, 2011.

ATF Fire Protection Engineers were asked to utilize engineering analysis methods, including computer fire modeling, to assist with determining the route of fire spread and the events that led to the firefighter MAYDAY and subsequent Line of Duty Death.

Download the REPORT HERE

BACKGROUND:

Working closely with the Post Incident Analysis Team, the ATF Fire Research Laboratory created a computer simulation of the garden apartment building using Fire Dynamics Simulator (FDS). FDS is a computational fluid dynamics (CFD) modeling program developed by the National Institute of Standards and Technology (NIST).

FDS utilizes mathematical calculations to predict the flow of heat, smoke and other products of fire. Smokeview, a post-processer computer program also produced by NIST, was then used to visualize the mathematical output from FDS. The most current available versions of both programs were used: FDS 5.5.3 and Smokeview 5.6. Below are photographs of the front and rear of the fire building next to an image of the same building constructed in FDS.

Figure 01. 30 Dowling Street

 

Figure 2. FDS representation of the front of 30 Dowling Circle showing the terrace (T), second (A) and third (B) levels.

 

The garden apartment building at 30 Dowling Circle was attached to two similar garden apartment buildings, one on each side. The fire damage was isolated to 30 Dowling Circle, so the exposure buildings were not included in the computer fire model. The entire six unit garden apartment building was modeled in FDS, including the patio and balconies on the rear of the building. FDS works by dividing a space into cubical “grid cells” for calculation purposes. FDS then computes various CFD calculations for each grid cell to predict the movement of mass, energy, momentum and species throughout a three-dimensional space.

The Dowling Circle model consisted of 2,560,000 total grid cells that were each 3.9 inch (10 cm) cubes. The model was used to simulate a total elapsed real time of 27.5 minutes, beginning before the 911 call and ending just after flashover of the third floor and the firefighter MAYDAY.

The model was synchronized in real time with the fireground audio throughout the duration of the fire.

Fiqure 03 and 04

 

FDS has been validated to predict the movement of heat and smoke throughout a compartment, however the accuracy of fire modeling depends on it being used appropriately by a trained user that is aware of its limitations. Due to lack of knowledge about the exact material properties for the various furnishings and other available fuels, a user-specified fire progression was used for this application.

For flame and fire gas movement after consumption of the original burning fuel packages, the fire model calculated smoke and ventilation flow paths through the building and was used to gain a better understanding of the rapid fire growth leading to flashover of the stairwell and third floor.

  • In addition, FDS was utilized to illustrate the complex route of fire spread through the building as verified by witness statements, firefighter interviews, photographs and burn patterns.
  • Input data for the computer model included heat release rate data and video from previous testing conducted by the ATF FRL and NIST.
  • Ambient weather data was also input into the model, including temperature, as well as wind direction and magnitude at the time of the fire. In addition, several alternative compartmentation scenarios were modeled to explore the possible effects of closed stairway apartment entrance doors on the spread of smoke and flames in the stairwell.
  • The statements of each firefighter were reviewed and their individual actions (breaking windows, opening doors, etc.) and observations (fire size, smoke conditions, etc.) were recorded on floor diagrams.

The actions and observations of the firefighters were then associated with specific times in the fireground audio to generate an overall event timeline. All events in the model are based on this master timeline of events. In addition, all photographs were time stamped and synchronized with the model. The Post Incident Analysis Team was consulted throughout the development of the event timeline and the computer fire model to ensure accuracy.

MODELING ANALYSIS:

1. Analysis of Fire Development in the Terrace Level

The fire originated on the stovetop of an occupied apartment on the right (south) side of the terrace level (apartment T2). Flames from a grease fire ignited kitchen cabinets, eventually causing the kitchen to flashover into the attached living room. Upon fire department arrival, a fully developed fire existed in the living room and kitchen of apartment T2. Prior to exiting the apartment, the occupant opened both the rear sliding door and the apartment entrance door in an attempt to ventilate smoke from the apartment.

 

Figure 06. A typical floor plan of the right side apartments at 30 Dowling Circle.

 

An analysis of the ventilation flow path through the apartment with FDS indicated that a significant unidirectional flow path existed up the stairs with an inlet at the rear terrace sliding door and outlet at the front apartment entrance door leading to the stairwell.

Figure 7. Smokeview frame of the rear of the building indicating the fire origin and smoke spread within the T2 apartment. Figure 8. View of smoke flow out of kitchen and open sliding glass door (center of photo) in the rear of apartment T2. Figure 9. Smokeview frame of flashover of the kitchen with flames extending into the living room. Flames also begin to extend out of the rear sliding door and impact the balcony above.

 

Figure 10. Ignition of second level balcony resulting from flame extension from living room.

 

This unidirectional flow path up the stairs is difficult to combat and is often experienced during basement fires as crews attempt to descend interior stairs. The model indicates sustained air temperatures in the stairwell of approximately 600 Fahrenheit (315 Celsius) at velocities of approximately 6 mph (2.7 m/s) from floor to ceiling as crews attempted to descend the stairs. This is consistent with statements from firefighting crews, who experienced extremely high heat conditions and indicated periodically seeing flames in the smoke layer flowing up the stairs.

The elevated air velocity of the stairwell flow path resulted in a high rate of convective energy transfer to the structural firefighting gear and high perceived temperatures as the firefighters attempted to descend the stairs. Firefighting crews flowed a hoseline down the stairs to combat the high temperatures; however no significant cooling was noticed by firefighters because the hose stream could not reach the seat of the fully developed fire in the kitchen area.

The crews were simply cooling the ventilation flow path without cooling the source of the energy in the apartment. It was not until a hose stream was directed through an exterior window and a portion of the fire was extinguished that gas temperatures and velocities began to decrease, allowing firefighters to make entry to the terrace apartment via the stairs.

Figure 12. Smokeview section frame showing unidirectional flow of approximately 600 Fahrenheit (315 Celsius) gases out of the stairwell entrance door

Front photo of unidirectional flow of smoke up stairwell from apartment T2. Note the high volume of smoke from floor to ceiling as the stairwell door serves as the flow path outlet. The ground ladder in the foreground was used to rescue an occupant on the third floor trapped by heavy smoke in the stairwell. (Refer to Figure 014)

Figure 014. Front photo of unidirectional flow of smoke up stairwell from apartment T2. Note the high volume of smoke from floor to ceiling as the stairwell door serves as the flow path outlet.

 

The first arriving engine, E-11, was staffed with a Captain, Lieutenant, Driver/Operator, and a Firefighter. Upon arrival at 1820 hours, the Captain gave a brief initial report describing a three story garden apartment with smoke showing from side Alpha: “The Captain of E-11 will have Command and we are initiating an aggressive interior attack with a 1 ¾” hand line”. Command also instructed the second due engine to bring him a supply line from the hydrant. 

A female resident (victim # 1) appeared in a third floor apartment window, Alpha/Bravo side (Apt. B-1), yelled for assistance, and threatened to jump. Smoke or fire was visible from any of the third floor windows. At 1823 hours, Command advised Dispatch that he had a rescue and that he was establishing Limited Command. Fire Dispatch was in the process of upgrading the response profile to an apartment fire with rescue when the responding Battalion Chief requested that the fire box be upgraded to a fire rescue box. While the Firefighter and Lieutenant prepared for entry into the building, the Captain and Driver/Operator extended a ladder to the 3rd floor apartment window and rescued the resident. The first attempt by the Firefighter and Lieutenant to make entry into the side Alpha entrance was unsuccessful due to the extreme heat and smoke conditions.

The second due engine, E-10, arrived at 1823 with staffing of a Captain, Lieutenant, Driver/Operator, and a Firefighter. At 1823, E-10’s crew brought a 4″ supply line to E-11 from the hydrant at Deanwood Rd. and Dowling Circle and assisted the first-in crew with fire attack.

  • The Captain from E-10 conferred with Command and was instructed to advance a second 1 ¾” hand line.
  • The window to the first floor right apartment (Apt. T-2) was removed, and the second 1 ¾” line was advanced to the building by the crew of E-10.
  • Fire attack was initiated through the removed window. At 1827, Command requested a second alarm.

At this time, heat and smoke conditions just inside the front door improved enough to allow the Firefighter and Lieutenant from E-11 to make entry through the front door and into the stairwell. There they encountered heavy, thick black smoke and high heat conditions coming up the stairs from the terrace level apartment. The Lieutenant reported that the doorway to the first floor apartment was orange with fire and he had to fight his way through heavy heat and smoke conditions to attack the fire in the first floor right apartment (Apt. T-2). Entry was made approximately 3 feet into the doorway when the Firefighter’s low air alarm began to sound, and he exited the building. A member from E-10’s crew replaced the Firefighter from E-11 on the hose line.

At the same time, the Captain from E-11 proceeded to the rear of the structure to complete his initial 360 degree size up. He noted that there was fire emanating from the open sliding doors on the first floor Charlie/Delta apartment (Apt. T-2), extending to the balcony above. E-1, staffed by a Captain, Driver/Operator, and two Firefighters arrived and completed the hookup of the supply line that had been laid to the hydrant by E-10. The rest of Engine 1’s crew grabbed tools and an extension ladder and reported to the Charlie side of the building.

Figure 015 Charlie Side ( Rear) Extension

The Photo above referenced as  Figure 015 shows conditions  from rear of flames in apartment T2 and extension to the balcony above. Note the relative minimal volume of smoke as the sliding door serves as the inlet for ventilation into the apartment. The smoke and heat is flowing in from the rear, through the apartment and up the stairs.

This unidirectional flow path up the stairs is difficult to combat and is often experienced during basement fires as crews attempt to descend interior stairs.

  • The model indicates sustained air temperatures in the stairwell of approximately 600 Fahrenheit (315 Celsius) at velocities of approximately 6 mph (2.7 m/s) from floor to ceiling as crews attempted to descend the stairs.
  • This is consistent with statements from firefighting crews, who experienced extremely high heat conditions and indicated periodically seeing flames in the smoke layer flowing up the stairs.
  • The elevated air velocity of the stairwell flow path resulted in a high rate of convective energy transfer to the structural firefighting gear and high perceived temperatures as the firefighters attempted to descend the stairs.

Firefighting crews flowed a hoseline down the stairs to combat the high temperatures; however no significant cooling was noticed by firefighters because the hose stream could not reach the seat of the fully developed fire in the kitchen area.

The crews were simply cooling the ventilation flow path without cooling the source of the energy in the apartment.

It was not until a hose stream was directed through an exterior window and a portion of the fire was extinguished that gas temperatures and velocities began to decrease, allowing firefighters to make entry to the terrace apartment via the stairs.

Plan view of flow path and temperatures within the apartment. Note the location of the seat of the fire and the location of initial hose stream application down the stairs.

Figure 016

 

Photograph of hoselines being positioned at the stairwell entrance door and front window. Note the heavy smoke venting from all front openings in apartment T2. (Figure 017)

Figure 017 Alpha Side Entry Door

 

Figure 017  Hoselines being positioned at the stairwell entrance door and front window. Rapid Fire Progression Leading to Flashover of the Third LevelFlames extended upwards from the T2 apartment sliding door and ignited the rear balconies of the second and third level apartments above.
 
Fire on the second floor balcony extended into apartment A2 by failing the sliding glass door and igniting vertical plastic slat curtains that were suspended above.As crews searched within the second floor apartment, they noted seeing the burning curtains on the floor with flames extending to a nearby couch (containing polyurethane foam padding) adjacent to the sliding doorway.
 
The fire continued to grow unsuppressed and spread to a second couch as interior firefighting crews were engaged in rescuing two victims from the living room in the second floor apartment.Personnel stated that at this point fire conditions seemed to improve, suggesting that crews were making progress extinguishing the fire. (The first arriving attack crew reported that they were able to see apparatus lights through the sliding doors on Charlie side, which indicated to them that smoke and fire conditions were improving.)Truck 1, a tiller unit staffed by a Lieutenant, two Driver/Operators, and a Firefighter, arrived on side Alpha and immediately began search and rescue operations.
 
Windows on the second floor Alpha/Delta side apartment (Apt. A-2) were vented and ladders were thrown to gain access. T-8 arrived at the alley on side Charlie. E-1 extended a ground ladder to the third floor balcony on the Charlie/Bravo side of the structure (Apt. B-1), and made access to the apartment to search for additional victims.They noted fire venting from the first floor Charlie/Delta apartment (Apt. T-2) out of the sliding glass doors progressing upwards towards the balcony on the second floor.
 
Upon entering the apartment, they conducted a primary search and noted minimal heat with light smoke conditions.The crew accessed the hallway via the apartment entry door and noticed an increase in the temperature and the amount of smoke.They immediately closed the door and exited the apartment via the ground ladder.Upon exiting the apartment, E-1’s crew observed E-292 on the scene with a hand line extending into the apartment of origin, (first floor, Charlie/Delta side, Apt. T-2).
 
The officer on E-1 noted white smoke coming from the unit.Having already laid a supply line from the intersection of the alley and Deanwood Road, E-292’s crew extended a 1 ¾” hand line into the apartment of origin. Moderate fire conditions with zero visibility were encountered, and they reported feeling a great deal of heat on their knees as they crawled through the apartment.The Lieutenant and the Firefighter from Truck-1 entered Apartment A-2 via a second floor bedroom window (Alpha/Delta side) and began a search for additional victims. As they traversed the living room area they found an unconscious male resident (victim #2).
 
At 1836 hours, the Lieutenant notified Command via an urgent transmission that a victim had been located and they needed assistance with evacuation. The Lieutenant and Firefighter noted a small fire in the rear corner near the victim as they exited the room. The crew returned to the bedroom from which they had entered and closed the door behind them. Victim #2 was then evacuated from the apartment via a ground ladder through the bedroom window, and transferred to EMS personnel on side Alpha.
 
Figure 019 Flame extension and suppression efforts at the rear of the structure. Flames caused the second level glass slider to fail and ignite plastic curtains in the doorway located
 

Figure 019

 
 

The middle level apartment (A2) entrance door was opened by a second search crew around the same time as the second couch ignited, creating a ventilation flow path from the second floor balcony, through the apartment, and upwards into the stairwell (third floor). This flow path follows the same general route through the apartment and into the stairwell as was seen in the terrace level apartment below. Squad 303’s crew arrived on scene after the bulk of the fire in the terrace level apartment had been suppressed and appeared to be under control. The crew entered the front stairwell, which had minimal smoke up to the second level and the crew began to systematically search the building.

Squad 303’s crew proceeded to search two apartments before entering the third floor right side apartment to conduct a search, leaving the entrance door open. It should also be noted that carpeting impacted the bottom of the door and prevented the apartment entrance doors on the second and third levels from closing automatically. The entry doors had to be actively pushed closed to overcome the friction of the carpet.

 

Photo depicting building smoke and fire conditions around the arrival of Squad 303.

Note the lack of heavy smoke or fire in the stairwell or terrace level.

There is also no indication of the growing fire in the second (middle) level apartment.

 

 

 

When Squad 303’s crew of two firefighters entered the third level apartment (B2), smoke was banked about halfway down the walls with moderate visibility. The crew could clearly see the floor of the apartment without the need to crawl below the smoke layer to search. Squad 303’s crew was unaware of the flames spreading across the two couches in the second floor apartment below them. The crew split in order to search the apartment faster, with one firefighter searching the front bedrooms and the officer searching the kitchen and living room.

As flames in the second level began to rollover into the apartment entranceway, the smoke layer in the third level quickly dropped to the floor with a rapid increase in temperature. With Squad 303’s crew searching above, flames began to extend into the stairwell, supplied by sufficient ventilation flowing through the apartment. This combination of fuel, heat and oxygen rich fresh air resulted in a rapid increase in heat release rate and flashover of the second level apartment followed by full room involvement.

The open entrance doors on the second and third levels created a ventilation flow path through the second floor apartment, into the sealed stairwell and up through the third floor apartment directly above. The flames followed this flow path and extended from the second floor, through the stairwell and into the living room area of the third floor apartment. Flashover of the third floor occurred approximately 30 seconds after the second floor experienced flashover.

Figure 026 and 027

 

Rollover from the second level apartment into the stairwell.

 

 
 
Flames followed the ventilation flow path and extend into the third floor apartment, resulting in ignition of the couches just inside the doorway.

 

 

    

 

Command sounded the building evacuation tones as flames extended into the hallway and up to the third level apartment.

Two couches just inside the entrance door on the third level ignited, blocking the primary means of egress for both firefighters from Squad 303. Upon hearing the evacuation horns from the trucks, the second firefighter from Squad 303 (searching the front bedrooms) attempted to exit the apartment via the apartment entrance door, however he was blocked by flames in the living room and stairwell.

Trapped in the bedroom, the firefighter bailed out headfirst down a ground ladder on the front side from the third floor. Squad 303 officer’s means of egress through the apartment entrance door was also blocked by the flames in the living room and stairwell. There were no windows located in the rear of the apartment.

The only means of escape was the balcony slider, however the entire balcony was engulfed in flames from the fully involved apartment below. With both escape routes blocked by flames and experiencing extremely high heat conditions, Squad 303’s officer requested assistance and declared a MAYDAY from the rear of the third floor apartment.

Firefighters re-entered the structure to combat the fire and locate the trapped firefighter. The downed firefighter was eventually located on the third level just inside the sliding glass door and was removed to the rear balcony. The firefighter was then extricated in a stokes rescue basket down the aerial ladder of a truck located in the rear, where he was subsequently transported to the hospital.

Effects of Compartmentation on Fire Spread

The Post Incident Analysis Team requested that alternate modeling scenarios be conducted to explore the effects of compartmentation on fire spread throughout the building.

The team specifically wanted to know how the ventilation flow paths through the stairwell would differ if the second or third level apartment entry doors were shut after entering/leaving the apartments. Two alternate computer fire modeling scenarios were conducted.

The first alternative modeling run featured the exact same fire scenario, except the second (middle) level apartment door was closed after the last victim was removed from that apartment. The apartment entry doors from the stairwell were fire-rated doors constructed of solid wood.

  • As soon as the door is shut, the ventilation flow path through the apartment and up the stairwell is blocked.

 

Shutting the second level apartment door blocks the flow path and flame extension into the stairwell. 

Even with the third floor apartment door left open, the model indicates that the stairwell and third floor remain tenable for firefighters. Flames eventually extend from the third floor balcony into the apartment, however the escape routes through the stairwell and the front apartment windows are accessible.           

The model indicates that closing the second level apartment door prevents the flow of smoke, heat and other products of combustion from entering the stairwell, thus preventing flashover of the stairwell and the third level. As long as the second floor entry door remains shut, the model indicated that the conditions within the stairwell and third floor remain tenable for firefighters, even with the third floor apartment door open.

A second alternative modeling scenario was conducted where the third level entrance door was closed after crews made entry to search the apartment.The same fire conditions from the actual model were used.When the door remained closed, the outlet of the ventilation flow path was blocked at the top of the stairs. Without a complete flow path, there wasn’t sufficient oxygen flowing through the second floor apartment to support extended burning in the stairwell.

Consequently after flashover of the second floor, the flames in the stairwell only exist momentarily before consuming all available oxygen and becoming ventilation limited.The fire model indicated that temperatures within the third floor apartment stayed tenable for firefighters, even with a fully developed fire on the second floor and flames in the stairwell.

Flames would eventually extend up the rear balcony to the third level, however they would not block egress through the living room and front windows of the apartment.By closing the apartment door on the third floor and blocking the outlet for fire gases emanating from the second floor apartment, the third floor apartment remains tenable for firefighting crews and the temperatures only briefly spike in the stairwell before the fire becomes ventilation limited.The ventilation flow through the apartments results in an increased burning rate within both the second and third levels, as well as the stairwell.                     

Results of each modeling scenario describing extent of flame spread

Results of each modeling scenario describing extent of flame spread.

 
 
 
 
 
 
 
 
 
 
The Effects of Compartmentation on Fire Damage to the StructureThe impact of compartmentation on fire and smoke spread is evident by examining the post-fire damage throughout the structure. While other factors contributed to the relative fire damage, including fire department overhaul and relative apartment configuration, analyzing the damage to the building and the position of the apartment entry doors provides insight on the benefits of compartmentation.

By closing apartment unit entrance doors and interior hollow core doors, one can slow or even block the ventilation flow path through the structure, thus significantly reducing the rate of fire spread. The photos below represent the post-fire damage in all six apartments within the fire building. Four of the six apartment entry doors were open for the majority of the fire and the relative difference in damage is clearly evident.

Terrace level stairwell landing looking into T1 (left) and T2 (right) apartments.

 

Door Closed……Door Open

 

 

Using doors to compartmentalize and limit fire and smoke spread in a structure is not limited to fire-rated entrance doors. Interior hollow core doors also offer considerable protection for compartmentation purposes.

A search crew utilizing the Vent, Enter and Search (VES) technique through a front window used a hollow core bedroom door to isolate themselves from the developing fire in the living room of apartment A2.

As the crews removed the second victim from the living room to the bedroom, they shut the bedroom hollow core door behind them.

The living room soon experienced flashover followed by full room involvement, however the bedroom remained isolated from the heat and smoke for the duration of the fire. The photos below illustrate this effective use of compartmentation to protect firefighters during a search.

 
Controling the Doors during VES

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
SUMMARY:
While no fire model will exactly replicate a fire, this model provided insight on the route of fire spread, the rapid fire growth leading to flashover of the second and third level, and the benefits of compartmentation on slowing fire and smoke spread.
  • The unidirectional flow path up the stairs from the terrace level apartment resulted in a high rate of convective heat transfer to the firefighters initially attempting to descend the stairs, making attacking the seat of the fire very difficult.
  • The model then supported the fact that the main stairwell acted as an open channel for fire and smoke spread between the second and third levels, resulting in flashover of the third level in approximately 30 seconds after the second level.
  • This rapid fire growth leading to flashover is supported by photographs, witness statements and fireground audio.
  • The model was then utilized to explore the effects of compartmentation using apartment entrance doors.
  • The FDS model supported the scene observations and indicated that shutting the entrance doors blocked the flow of buoyancy driven fire gases through the structure, ultimately preventing fire extension to the third floor apartment via the stairwell.
  • The FDS model was utilized as part of the overall engineering analysis of this tragic fire and allowed for a better understanding of the events that led to the firefighter MAYDAY and subsequent Line of Duty Death.
  • The model was also used as an educational tool providing insight on potential methods of preventing similar tragedies in the future.
  • The results of this engineering analysis are intended to be reviewed by the Post Incident Analysis Team to assist in the creation of recommendations to mitigate the danger associated with future fire incidents.

References:

Second Alarm Apartment Fire, VA

No comments

Photo by Maxim Boldin

 
 
 
A second alarm fire occurred in a four-story apartment building in the 20500 block of Reserve Falls Terrace, Loudoun County, VA that took command of over 13 apartment units.
 
The fire was reported at 07:39 hours on Sunday morning November 20, 2011.
 
Arriving companies found heavy fire was coming from the building. Fire crews initiated an offensive attack but were forced to evacuate due to potential structural collapse considerations.
 
A second alarm was activated and a defensive attack was mounted until it was safe for crews to get back inside. Firefighters from Sterling, Lansdowne, Ashburn and Fairfax responded to the fire. Crews remained on the scene for several hours performing overhaul and checking for hot spots.
 
At least 13 units in the building were damaged, displacing over 26 occupants. There were no reported injuries.
 
 

Alpha Division Aerial View-Street Side

 

Bravo Division (note grade change from the Alpha to Charlie sides)

 

Fire Extension thru Roof at Bravo Division Charlie

 

Typical Interior Room Compartments

 
 

Typical Unit Floor Plans

 
 
 
Links
 

 

Operational Considerations at Garden Apartment Complex and Residencies

 Fire ground operations at Garden Apartment Complex and Multiple Occupancy Residencies require due diligence and well-coordinated multiple company operations that have well established operating protocols, clearly defined ( but flexible) company and response duties and an effective and well-practiced and experienced cadre of company and command officers.  

Due to the likely demands and complexities of evolving and expanding incident conditions at fire involving Garden Apartment type buildings and complexes, couple with the civilian life safety concerns due to occupancy density and numbers, immediate and timely resources are necessary to conduct multiple and concurrent functional assignments that demand effectiveness, efficiency and trained company compositions.

Strategy and Tactics at Garden Apartment Complex and Residencies required special instructions, insights and knowledge that goes well beyond the practices and methodologies typically deployed at single family residential fire incidents.

Multiple occupancy dwelling units, occupancy loads, multiple floors, building construction, structural systems and assemblies, construction and material, methods of construction and building and occupancy layouts and configurations results in fast spreading and extreme fire conditions, common avenues for internal and exterior fire travel, congested travel paths and access/egress points, multiple hose line deployment strategies with adequate fire flows, effective building laddering, forcible entry support and concurrent, mobile and skilled search and rescue  capabilities.

The ability to deploy and operate multiple hand lines is mission critical at fires in these multiple occupancy dwellings. As are a number of other strategic and tactical functions; but again, If the fire is controlled and goes out- all the other escalating, concurrent and immediate demands, needs and requests along with highest risk factors for survivability to occupants and firefighter alike diminishes rapidly and can be managed.

 Here are some discussion points to chat about around the kitchen table;

  • Are your engine companies effectively set up and outfitted to stretch out and deploy extended lines, multiple lines on common floors or within various floor elevations?
  • Have you and your company practiced coordinated multiple company search and rescue protocols for multiple occupancy floor areas?
  • Have you considered the needs, impacts and operational deployment for a RIT on a common floor during extreme fire conditions that required interior common hallway access and extraction of a firefighter in distress or incapacitated?
  • Do you have the capability to deploy and implement multiple companies for coordinated roof ventilation operations?  IF so, have they training together in the past?
  • How effective and knowledgably are you and your company in initiating and completing multiple trench, strip or louver roof ventilation cuts?
  • Are you aware of the signs for potential or imminent collapse for the various types of garden apartment buildings in your response area? Did you know there are different considerations based on the vintage, age and construction systems and assemblies utilized?
  • When was the last time you either pre-fire planned any of your garden apartment building or complexes? Or did a company walk-through?
  • Which ones are protected by a fixed sprinkler system?
  • Do you what the water fire flow capabilities are for the hydrants and system in any of these garden apartment building or complexes?
  • Have you done any table top exercises considering a standard alarm assignment fire, or an escalating multiple alarms incident?
  • Do you consider occupancy risk versus occupany type for the buildings you respond to?
  • Are your considering the effects of extreme fire behavior and the potential for wind driven fire conditions in your IAPs?
  • Are you considering the collapse and compromise potential for floor and roof assemblies in your assignments?
  • Are you fully prepared for immediate or multiple RIT needs and deployments?
  • Do you understand how these garden apartment buildings are constructed, configured and will impact your strategic and tactical assignments?
  • Do you have the right skill set for performing safely and effectively in your assigned role and responsibilities? If not, what are you going to do about that gap?

 

On Scene, All Hands with Civilians in Distress

No comments

2S MO B&J Brooklyn

Two Story Multiple Occupancy (Duplex) Brick & Joist Type III Building, 3,120 SF built CA 1910
FDNY All Hands Fire with Pre-Arrival video

  • As a first-arriving company, with both civilians in distress and indications of a working fire, what are the considerations, options and priorities of the company officer upon arriving at curb side?
  • What is the single most operational consideration the company officer must consider before deploying the assignment?

Alpha Street Side

 

Multiple Alarm Operations with Wind Driven Fire

No comments

The five alarm fire that ran through a seven story multiple occupancy (MO) apartment building in the Flatbush Section in the Borough of Brooklyn (NYC) this weekend considerably challenged operating companies of the FDNY as the fire was fueled and spread in rapid success due to significant wind conditions compounded by news reports that a door to the fire compartment was left open, thus allowing the developing fire conditions to intensify and escalate due to the wind driven conditions that were impacting the building, the fire compartment and initial operating companies.     

Aerial View of the Apartment Building

The seven-story MO Apartment building at 346 East 29th Street is reported to have had 70 apartments and was located midway in the city block. Arriving companies reported a fire on the number four floor and quickly deployed handlines and initiated primary search and rescue and other tactical assignments.   

Street View

First-due operations, from the initial alarm assignment’s arrival, the transmission of size-up communications and the accurate and timely deployment of companies to task assignments is mission critical to an evolving incident.     

The introduction of other challenges such as confronted by FDNY at this alarm further magnify the importance of effective command risk assessment, building size-up, effective and efficient company assignments and deployments with adequate resources (staffing and companies) to intervene with the fire dynamics and growth of an initial developing room and contents to an extending and escalating structure fire.      

       

YouTube Preview Image       

   

Take a few minutes to listen to the radio transmissions on the audio file attached, paying particular attention to the exchange of dispatch communications, first-due size-up and actions, command transmissions and subsequent rapid transmittal of greater alarms, as fire ground operational conditions deteriorated due to the wind driven fire, fire extension, civilian’s in distress and rescue operations.   

Think about the way you would react, interface or address similar conditions and challenges at an alarm in your jurisdiction or department.   

  • Do you have the necessary skills and experience to address timely actions required of company and command officers at a wind drive fire incident?
    • Are you capable of addressing a large single family dwelling, or a large low rise MO apartment building? How about a townhouse or garden apartment complex building?
    • How familiar are you with strategic and tactical considerations wind drive fire incidents?
    • Are you aware of the recent research and operational factors and considerations coming out of emerging research from the NIST and UL?
    • How effective are your capabilities for operating at large scale multiple alarm incidents with your department’s resources, or with mutual aid or external agencies?
    • Have you trained and prepared to manage multiple alarm incidents?

      

Take some to time to gain some insights from this alarm; the communications and the challenges and make this a learning opportunity to gain some insights into wind drive fire theory and operational considerations.   

Here’s some mission critical links and references to make you a more effective and capable company and command officer.   

National Fire Academy On-Line Training Program   

Awareness of Command and Control Decision making at Multiple Alarm Incidents (Q297) 1.5 CEUs Enroll Now »  

This course is both a stand-alone course as well as the pre-course for the 6-day residential delivery of the National Fire Academy’s new Command and Control Decision Making at Multi-Alarm Incidents. Anyone interested in applying for the 6-day residential course must pass this pre-course with a score of 85 percent. The topics covered in this pre-course include: classical and naturalistic decision making, strategies for managing safety concerns at expanded emergency incidents, pre-incident preparation, resource allocation, effective use of on-site communications, set-up of an incident command post and post incident analysis.

NIST: Fire Fighting Tactics Under Wind Driven Fire Conditions: 7-Story Building Experiments. HERE  

 February 2008, a series of 14 experiments were conducted in a 7-story building to evaluate the ability of positive pressure ventilation fans, wind control devices and external water application with floor below nozzles to mitigate the hazards of a wind driven fire in a structure. Each of the 14 experiments started with a fire in a furnished room. The air flow for 12 of the 14 experiments was intensified by a natural or mechanical wind.. Each of the tactics were evaluated individually and in conjunction with each other to assess the benefit to fire fighters, as well as occupants in the structure. The results of the experiments provide a baseline for the hazards associated with a wind driven fire and the impact of pressure, ventilation and flow paths within a structure. Wind created conditions that rapidly caused the environment in the structure to deteriorate by forcing fire gases through the apartment of origin and into the public corridor and stairwell. These conditions would be untenable for advancing fire fighters. Each of the tactics were able to reduce the thermal hazard created by the wind driven fire. Multiple tactics used in conjunction with each other were very effective at improving conditions for fire fighter operations and occupant egress. Fire departments that wish to implement the tactics used in this study will need to develop training and determine appropriate methods for deploying these tactics. Variations in the methods of deployment may be required due to differences in staffing, equipment, building stock, typical weather conditions, etc. There is uniformity however, in the physics behind the wind driven fire condition and the principles of the tactics examined. The data from this research will help provide the science to identify methods and promulgation of improved standard operating guidelines (SOG) for the fire service to enhance firefighter safety, fire ground operations, and use of equipment. The experiments were conducted by the National Institute of standards and Technology (NIST), the Fire Department of New York City (FDNY), and the Polytechnic Institute of New York University with the support of the Department of Homeland security (DHS)/Federal Emergency Management Agency (FEMA) Assistance to Firefighters Research and Development Grant Program and the United States Fire Administration.  

pdf icon Fire Fighting Tactics Under Wind Driven Fire Conditions: 7-Story Building Experiments. (58118 K)
Kerber, S. I.; Madrzykowski, D.  

NIST Wind Driven Fires Studies, HERE  

Smoke and heat spreading through the corridors and the stairs of a building during a fire can limit building occupants’ ability to escape and can limit fire fighters’ ability to rescue them.  Changes in the building’s ventilation or presence of an external wind can increase the energy release of the fire.  This can also increase the spread of fire gases through the building.  In some cases, such as the Cook County Administration Building fire in October 2003, the fire gas flow, into the corridors and the stairway prevented fire fighters from suppressing the fire from inside the structure.  This fire resulted in 6 building occupant fatalities and fire fighter injuries in the stairway.  The Fire Department of New York City has experienced many wind driven fire incidents which have resulted in fire fighter fatalities and injuries.  

 

Postings from Buildingsonfire.com

 

Direct link to the Wind Driven Fire Research Postings on Buildingsonfire.com  HERE 

NIST Wind Driven Fire Simulation Video

NIST Wind Driven Fire Simulation Video Wind Driven Fires Smoke and heat spreading through the corridors and the stairs of a building during a fire can limit building occupants’ ability to escape and can limit fire fighters’ ability to rescue them.  Changes in the building’s ventilation or presence of an external wind can increase the [...]  

Jan, 29 2011 0 Comments Full Story

Positive Pressure Ventilation Research

Positive Pressure Ventilation The objective of this NIST research is to improve firefighter safety by enabling a better understanding of structural ventilation techniques, including positive pressure ventilation (PPV) and natural ventilation, and to provide a technical basis for improved training in the effects of ventilation on fire behavior by examining structural fire ventilation using full-scale fire experiments with and [...]  

Jan, 14 2011 0 Comments Full Story

NIST Wind Driven Fires Programs

Wind Driven Fires Wind blowing into the broken window of a room on fire can turn a “routine room and contents fire” into a floor-to-ceiling firestorm. Historically, this has led to a significant number of firefighter fatalities and injuries, particularly in high-rise buildings where the fire must be fought from the interior of the structure. [...]  

Jan, 14 2011 0 Comments Full Story

Wind Driven Fires

 A million dollar Baltimore County, Maryland  home was destroyed Sunday December 13, 2009  by a fire that tore through the 4,700-square-foot structure with such intensity that firefighters were forced to battle the flames from the exterior. Shortly after 21:00 hours, Baltimore County Fire Dispatch alerted crews for Fire Box 50-2 at 12607 Nancy Lee Court [...]  

Tactical Patience and the New Considerations of Ventilation on Fire Behavior in Legacy and Contemporary Residential Construction  on CommandSafety.com HERE, with insights into the new UL Impact of Ventilation on Fire Behavior in Legacy and Contemporary Residential Construction

   

ALARM INFORMATION
FDNY
   Brooklyn, N. Y. 02/19/11 @ 18:45 hrs.
Flatbush Section Box 2439 address: 346 East 29th St. between: Ave. “D” & Clarendon Rd.
     

2439 @ 18:42
Engs. 255, 281, 217 act. 310
T. Lad. 157, Lad. 147
Batt. 41      

10 – 75 – 2439 @ 18:46
Ladder 113 is designated as the “FAST” Truck
Eng. 249
Rescue Co. #2
Squad Co. #1
Batt. 48
Division 15      

Fire Building:
6 Story Brick 100 x 100 O/M/D ( orig. reported )
7 Story Brick 100 x 100 O/M/D ( actual size up )      

All – Hands:
7 – 5 – 2439 @ 18:48
Batt. 41 reports: All – Hands upon arrival, extra Engine & Truck
Fire 4th floor of a 6 Story Brick occupied multiple dwelling
Engine 250 / Ladder 174 s/c      

“Batt. 41 to Brooklyn, Transmit a 2nd Alarm, We also transmitting a 10-70 ( water relay )      

2nd Alarm:
2 – 2 – 2439 @ 18:53
Engs. 310, 240, 283 ( Eng. 310 designated Water Resource Unit )
T. Lad. 159, Lad. 149
Eng. 284 w/ Satellite 3
Batt. 38 “Safety Officer”
Batt. 33 “Resource Unit Leader”
Rescue battalion / Safety Battalion
Fieldcom 1 / Tactical Support Unit #2      

@ 18:58
Batt. 41 to Brooklyn, We have a “May-Day” transmitted from the Fire Apt. We’re putting the “FAST” Truck to work. Assigned another “FAST” Truck, Tower Ladder 159 is assigned new “FAST” Truck      

@ 19:13
Division 15 reports: “May-Day” member located and removed from Fire Bldg. We have fire on the 4th & 5th floors out the rear.
4 – lines stretched, 4 – lines in operation. Fire’s Doubtful.      

3rd Alarm:
3 – 3 – 2439 @ 19:15
Engs. 309, 323, 257, 330
Lad. 123, T. Lad. 170
Batt. 58
Batt. 44 “Staging Manager”
Air Re-Con Chief “grounded” due to winds
Mask Service Unit #1
Staging Area: Clarendon Rd. & Nostrand Ave.      

@ 19:20
Division 15: Box 2439, We have fire on the 4th; 5th; & 6th floors and into the Cockloft. All members being removed from the upper floors, setting up the Tower Ladders.      

@ 19:27
Special Call ( 2 ) additional Battalion Chief’s
Batt. 40 act. 58, Batt. 32 are s/c      

@ 19:30
Special Call a “High Rise Nozzle Co.” Eng. 254 assigned      

@ 19:36
Special Call ( 2 ) Tower Ladders
Tower Ladder 144 act 153 & Tower Ladder 120 are s/c      

4th Alarm:
4 – 4 – 2439 @ 19:38
Engs. 276, 220, 247, 321
Batt. 57 “Planning Chief”
Eng. 262 w/ Incident Management Vehicle
Car 4: Chief Robert Sweeney “Chief of Operations”      

@ 20:39
Fieldcom 1: Progress Report for the 4th Alarm, Box 2439, Car 4, Chief Sweeney reports:
Fire in a 6 Story Brick occupied multiple dwelling. ( 3 ) Tower Ladders in operation in the rear of the Fire Bldg. ( 1 ) Tower Ladder in operation in the front of the Fire Bldg. Setting up 2nd Tower Ladder in the front of the Fire Bldg. ( 1 ) Stang in operation in the rear. Have ( 3 ) floors of fire out the rear of the Fire Bldg. Doubtful Will Hold.      

@ 20:44
Fieldcom 1: By orders of Chief Kilduff, transmit the 5th Alarm.
Special Call ( 2 ) additional Engines above the 5th Alarm for “Brand Patrol”      

5th Alarm:
5 – 5 – 2439 @ 20:44
Engs. 234, 280, 282, 227
Engs. 290 & 214 s/c for “Brand Patrol”
Car 3: Chief Edward Kilduff “Chief of Department”      

@ 20:58
Fieldcom 1: Progress Report for the 5th Alarm, Box 2439, Car 4, Chief Sweeney reports:
Primary Searches on the 4th floor are negative except for Apt. 4 “adam”      

@ 21:13
Fieldcom 1: Special Call ( 2 ) additional Trucks to the Staging Area.
Ladder 132 & Tower Ladder 111 are s/c      

@ 21:22
Fieldcom 1: At this time, We’re releasing Rescue #2 & Squad #1      

@ 21:26
Fieldcom 1: Progress Report for the 5th Alarm, Box 2439, Car 4, Chief Sweeney reports:
All members have been removed from the Fire Bldg. ( 3 ) Tower Ladders in operation in the front of the Fire Bldg. ( 2 ) Tower Ladders & ( 1 ) Stang in operation in the rear of the Fire Bldg. Still have heavy fire on the 4th; 5th; & 6th floors. This will be a pro long operation. Still Doubtful.      

@ 22:15
Fieldcom 1: Progress Report for the 5th Alarm, Box 2439, Car 3, Chief Kilduff reports:
( 3 ) Tower Ladders in operation in the front of the Fire Bldg.
( 2 ) Tower Ladders and ( 1 ) Multi-Versal in operation in the rear of the Fire Bldg. Fire is darkening down on the 4th & 5th floors in the rear. Fire is Still Doubtful.      

@ 22:58
Fieldcom 1: Progress Report for the 5th Alarm, Box 2439, Car 4, Chief Sweeney reports:
Probably Will Hold
The Bldg. has been changed to a 7 Story Bldg. Fire was on the 5th; 6th; & 7th floors and Cockloft.      

@ 23:10
Fieldcom 1: Special call Eng. 233 with Mobile Command 1      

@ 23:12
Fieldcom 1: Special Call ( 1 ) Division Chief, & ( 3 ) Battalion Chiefs for “relief”
Batt. 4, Batt 31 act. 41, Batt. 49 are s/c
Division 1 s/c      

@ 23:18
Fieldcom 1: Special Call ( 3 ) additional Engine’s, ( 3 ) additional Tower Ladders for “relief”
Engs. 330, 248, 220
T. Lads. 107, T. Lad. 161 act. 157, T. Lad. 15 act. 131      

@ 01:58
Fieldcom 1: By order’s of Division 1, Fire is Under Control.      

(Job Duration: 7 hrs./16 mins.)      

Note: 2 Engines, 2 Trucks, 1 Batt. Chief will be Special Called on intervals to support a “watch line”      

( 1 ) 10-45 Code 1 (deceased was located in the Fire Bldg.)   